UserGuideRevision1.12
www.beijerelectronics.com
10
3. MechanicalInstallation
3.1. General
• TheDriveshouldbemountedinaverticalpositiononly,onaflat,flameresistant,vibrationfreemountingusingtheintegral
mountingholesorDINRailclip(FrameSize2only).
• TheDrivemustbeinstalledinapollutiondegree1or2environmentonly.
• Donotmountflammable
materialclosetotheDrive
• Ensurethattheminimumcoolingairgaps,asdetailedinsection3.5and3.7areleftclear
• EnsurethattheambienttemperaturerangedoesnotexceedthepermissiblelimitsfortheDrivegiveninsection10.1
• Providesuitableclean,moistureandcontaminant
freecoolingairsufficienttofulfilthecoolingrequirementsoftheDrive
3.2. BeforeInstallation
• CarefullyUnpacktheDriveandcheckforanysignsofdamage.Notifytheshipperimmediatelyifanyexist.
• Checkthedriveratinglabeltoensureitisofthecorrecttypeandpowerrequirementsfortheapplication.
• TopreventaccidentaldamagealwaysstoretheDriveinitsoriginal
boxuntilrequired.Storageshouldbecleananddryandwithinthe
temperaturerange–40°Cto+60°C
3.3. ULCompliantInstallation
NotethefollowingforUL‐compliantinstallation:
• ForanuptodatelistofULcompliantproducts,pleaserefertoULlistingNMMS.E226333
• Thedrivecanbeoperatedwithinanambienttemperaturerangeasstatedinsection10.1
• ForIP20&IP40units,installationisrequiredina
pollutiondegree1environment
• ForIP55&IP66units,installationinapollutiondegree2environmentispermissible
• ULListedringterminals/lugsmustbeusedforallbusbarandgroundingconnections
3.4. Mechanicaldimensions
3.4.1. IP20Units
Drive
Size
A/Height B C D E F/Depth G/Width H I J Weight
mm mm mm mm mm mm mm mm mm mm kg
2 221 207 137 209 5.3 185 112 63 5,5 10 1,8
3 261 246‐ 247 6 205 131 80 5,5 10 3,5
MountingBolts
AllFrameSizes: 4xM4
TighteningTorques
ControlTerminalTorqueSettings: AllSizes:0.8Nm
PowerTerminalTorqueSettings: AllSizes:1Nm