Connection
Beijer Electronics, MAEN843A 11
Cable Routing in Cable Entrance Area
Cable routing makes it possible to adapt the M70 to suit either a right- or left-
handed user better.
After opening the cable entrance area, the connecting lines can be routed as de-
scribed in the following section. Before opening the M70 please pay attention
to the safety instructions below.
Instructions for opening the cable entrance area:
– Place the M70 with the display facing down onto a plane and clean table
(preferable on ESD pad) and take care not to damage the M70 and its oper-
ating elements.
– For opening and closing the cable entrance area a Phillips size 2 screwdriver
is used.
Instructions for modifications in the cable entrance area:
– Unplug the main connector (S22) by pulling on its wires with your fingers.
Do not use any sharp objects.
– For unplugging the RJ-45 jack (S11or S4), actuate the locking lever:
Make sure that the connectors S22 and S4 / S11 correctly snap in when you plug
them in. Otherwise the emergency stop functionality (S22) or the correct shield-
ing (S4 / S11) might not be given anymore.
Instructions for closing the cable entrance area:
– Make sure that the sealing is clean, not damaged and correctly positioned in
the cable entrance area.
– Make sure that no cables are squeezed in.
– Make sure that the cover of the cable entrance area is attached again with all
6 screws (torque: 0.4 - 0.5 Nm).
Otherwise the protection degree cannot be guaranteed.