Installation
4.
Connect the cables in the specified order, according to the drawing and steps
below.
Caution:
Ensurethattheoperatorpanelandthecontrollersystemhavethesameelectrical
grounding(referencevoltagelevel),otherwiseerrorsincommunicationmay
occur.
Theoperatorpanelmustbebroughttoambienttemperaturebeforeitisstarted
up. Ifcondensationforms,ensurethattheoperatorpanelisd rybeforeconnecting
ittothepoweroutlet.
Ensurethatthevoltageandpolarityofthepowe rsourceiscor rect.
Useonlyshieldedcommunicationcables.
Separatehighvoltagecablesfromsignalandsupplycables.
24V DC
RS422/RS485
24V DC
1
CF CARD
B
A
C
D
RS232
Controller
Power
Ethernet
Connect cable A.
Connect cable B, using an M5 screw and a grounding conductor (as short
as possible) with a cross-section of minimum 2.5 mm
2
.
Connect cable C.
Connect cable D.
5.
Carefully remove the laminated film over the operator panel display, to avoid
static electricity that could damage the panel.
BeijerElectronics, MAEN995