APPLICATION NOTE AN-BEI-P2-050
AN-BEI-P2-050 Open Loop Permanent Magnet Motor Control
Firmware Overview – Additional Parameters and Settings:
Additional Parameter information to that provided in the standard Beijer Frequency Inverter P2 manual is as
follows:-
Set to ‘201’ for access to PM motor control parameters.
PM motor selection setting (in P4-01) and menu 7 are
not visible when other value (than 201) is set.
0, 1, 2: See Std Guide
3: PM Motor Control
Selects the motor control method.
Set to ‘3’ for Sensor-less PM motor control
Motor Stator Resistance (phase –phase).
Measure with ‘auto-tune’ or enter manually.
Inductance Per Phase.
‘d’ component of armature winding inductance from
the d-q linear model.
Measure with ‘auto-tune’ or enter manually.
Inductance Per Phase.
‘q’ component of armature winding inductance from
the d-q linear model.
Measure with ‘auto-tune’ or enter manually.
System Load Inertia to Motor Inertia Ratio. Entered into
P7-10 as:
P7-10 = (J
Tot
/ J
Mot
) . 10
Motor magnetising time at start.
Time following drive enable to establish magnetising
flux in motor windings in order to accurately phase
motor shaft.
Boost current applied at start-up, as % of motor rated
current (P1-08)
Frequency range for applied boost current (P7-14) as %
of motor rated speed (P1-10)